GE Industrial Solutions EPM1500 Single Point Submetering System User Manual
Page 43
CHAPTER 4: COMMUNICATIONS
EPM 1500 SUB-METER– INSTRUCTION MANUAL
4–11
Note
1.
32-bit floating point numbers are as per the IEEE 754-1985 standard.
2.
Registers 0X0063 to 0X025E are all read-only and cannot be modified. They break
down as follows:
•
Registers 0X0064 to 0X0122 are not real-time, but are populated with
stored interval data based on user inputs to registers 0X0040 to 0X0043.
•
Registers 0X0162 to 0X025E are all real-time data registers.
07D1
2001
Demand Window Offset
16-bit Unsigned Integer
5, 15, or 30 minutes available
07D2
2002
I Multiplier Type Offset
16-bit Unsigned Integer
Internal calibration value
07D3
2003
Number of Pulse Counters Offset
16-bit Unsigned Integer
Number of external pulse inputs installed
07D4
2004
Overlap Offset
16-bit Unsigned Integer
Number of adjacent demand windows
that are averaged to determine peak
demand
07D5
2005
Number TOU's Offset
16-bit Unsigned Integer
Number of different TOU periods defined
in the time-of-use table
07D6
2006
MDT_M_TABLE_REG_START
16-bit Unsigned Integer
07D7
2007
NUM_MDT_M_TABLE_COLUMNS
16-bit Unsigned Integer
07D8
2008
NUM_MDT_M_TABLE_REGS
16-bit Unsigned Integer
07D9
2009
MDT_M_TABLE_REG_END
16-bit Unsigned Integer
* 32-bit floating point register.
+
32-bit long integer - Range: 00000000h to FFFFFFFFh
Table 4–1: Modbus Memory Map (Sheet 4 of 4)
Hex
Addr
Addr
Description
R/W
Units
Notes