3 modbus memory map, 1 memory map, Modbus memory map -8 – GE Industrial Solutions EPM1500 Single Point Submetering System User Manual
Page 40: Emory
4–8
EPM 1500 SUB-METER– INSTRUCTION MANUAL
CHAPTER 4: COMMUNICATIONS
4.3
Modbus Memory Map
4.3.1
Memory Map
The Modbus memory map is shown below.
Table 4–1: Modbus Memory Map (Sheet 1 of 4)
Hex
Addr
Addr
Description
R/W
Units
Notes
Fixed Value Registers (Read Only)
000
0
+
0000
Meter Serial Number
R
32-bit long integer
0002
+
0002
Meter Serial Number Extension
R
Returns same value as address 0000
32-bit long integer
0004
+
0004
Meter Version Number
R
32-bit long integer
0006
+
0006
Meter Version Number Extension
R
Returns same value as address 0000
32-bit long integer
0008
0008
Meter Modbus Address
R
---
8-bit Modbus Address in LSB
Setup Information
0009
0009
Baud Rate
R
000C
0012
Meter Status
R
---
Always 1 for Modbus.
000D
0013
Meter Ready
R
---
Always 1 for Modbus.
000E
0014
Number of Meters Configured
R
---
Always 1 for EPM 1500
000F
0015
Number of Real-Time Points
Configured
R
0010
0016
Number of Interval Points
Configured
R
Returns 0 if intervals are disabled
0011
0017
Number of Max/Min Points
Configured
R
Always returns 0
0012
0018
Maximum Number of Intervals
That Can Be Recorded
R
Dependent upon the number of
parameters optioned and the number of
meters returned in address 0015
0013
0019
Number of slots configured for
Transponder
R
0014
0020
Current slot being read in
Transponder
R/W
Interval Setup
0031
0049
Store Interval Length
R/W minutes
Interval length in minutes must be evenly
divisible into 60 (1, 2, 3, 4, 5, 6, 10, 12, 15,
20, 30, 60)
Read Clock
0032
0050
Internal Time - Hours/Minutes
R/W hours/
minutes
16-bit, Hours: 0-23 (bitmask = FF00)
Minutes: 0-59 (bitmask = 00FF
0033
0051
Internal Time - Seconds
R/W seconds
0034
0052
Internal Date - Month/Day
R/W month/day
0035
0053
Interval Date - Year
R/W year