3 confirming connection to the epm 1500, 4 logging into the meter, Onfirming – GE Industrial Solutions EPM1500 Single Point Submetering System User Manual
Page 37: Onnection, Epm 1500 -5, Ogging, Into, Eter
CHAPTER 4: COMMUNICATIONS
EPM 1500 SUB-METER– INSTRUCTION MANUAL
4–5
Z
Check the Echo typed characters locally option, as shown below.
4.2.3
Confirming Connection to the EPM 1
500
Z
To confirm a proper RS485 connection to the EPM 1500, enter the
following command:
attn -D
(followed by the [ENTER] key)
If meter is properly connected, it will respond with a serial number and poll
address. Once in Modbus mode, this command will no longer work.
For example, entering the command
attn -D
followed by the [ENTER] key returns:
60005866 256
for a meter with serial number 60005866 and poll address 256.
4.2.4
Logging into the Meter
Use the following procedure to login to the EPM 1500.
Z
Setup a ‘key macro’ in HyperTerminal by selecting the View > Key
Macros menu item.
Z
Click New and select an appropriate macro key sequence (ALT-1 is
used the example below.
Z
Enter the following command in the Action area:
attn -S[serialNumber] -5lEvElbAl
The password is -s5 followed by the LABLEVEL text spelled
backwards, with the vowels in upper case. This login string must
be followed by the ENTER command within the key macro.
Z
For example, for a unit with serial number 60005866, enter the
following text: