Table 9-A: Galaxy Power System 4812/24 Specifications
Electrical
AC Input
Input Distribution
592A2
596D
• 125A circuit breaker per 2-shelf cabinet
• 150A circuit breaker per 3-shelf cabinet
• 25A circuit breaker per rectifier for individual feeds
• 110 / 125A circuit breaker per 1-shelf cabinet
• 2 x 110 / 125A circuit breaker per 2-shelf cabinet
• 2 x 150A circuit breaker per 3-shelf cabinet
• 50A circuit breaker per rectifier for individual feeds
Minimum Wire Size
596A2
596D
• 2 gauge/35 mm
2
- 1 and 2-shelf cabinet
• 1/0 gauge/50 mm
2
- 3-shelf cabinet
• 10 gauge/6 mm
2
- per rectifier for individual feeds
• 2 gauge/35 mm
2
- 1-shelf cabinet
• 2 x 2 gauge/35 mm
2
- 2-shelf cabinet
• 2 x 1/0 gauge/50 mm
2
- 3-shelf cabinet
• 8 gauge/10 mm
2
- per rectifier for individual feeds
Cabinet Output -48V
Full Height
Half Height
Output Current
596A2
596D
55 - 800A
110 - 1,600A
50 - 400A
110 - 800A
System Output -48V
2 x Full Height
1 Half Height + 1 Full Height
Maximum System
Output Current
596A2
596D
55 - 1,200A
110 - 3,200A
55 - 1,200A
110 - 2,400A
3,520A
1
7,040A
1
1. With Galaxy Millennium Controller