beautypg.com

High power service manual for unit sizes 6x, 8 restore factory settings – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 20

background image

2.2.8 Restore Factory Settings

There are two ways to restore the drive to factory settings: Recommended restore and manual restore.
Please be aware that they have different impact according to the below description.

Recommended restore (via par. H-03 Restore Factory Settings)

1.

Select par. H-03 Restore Factory Settings

2.

Press [OK]

3.

Select [2] Restore Factory Settings

4.

Press [OK]

5.

Remove power to unit and wait for display to turn off.

6.

Reconnect power and the frequency converter is reset. Note that
first start-up takes a few more seconds

7.

Press [Reset]

Par. H-03 Restore Factory Settings restores all except:
Par. SP-50 RFI Filter
Par. O-30 Protocol
Par. O-31 Address
Par. O-32 Drive Port Baud Rate
Par. O-35 Minimum Response Delay
Par. O-36 Max Response Delay
Par. O-37 Maximum Inter-Char Delay
Par. ID-00 Operating Hours to par. ID-05 Over Volt's
Par. ID-20 Historic Log: Event to par. ID-22 Historic Log: Time
Par. ID-30 Alarm Log: Error Code to par. ID-32 Alarm Log: Time

Manual restore

NB!
When carrying out manual restore, serial communication, RFI filter settings and fault log settings are reset.
.

1. Disconnect from mains and wait until the display turns off.

2a. Press [Status] - [Main Menu] - [OK] at the same time while power
up for keypad

3. Release the keys after 5 s

4. The frequency converter is now programmed according to de-
fault settings

The Manual Restore restores all except:
Par. ID-00 Operating Hours
Par. ID-03 Power Up's
Par. ID-04 Over Temp's
Par. ID-05 Over Volt's

High Power Service Manual for Unit Sizes 6x

19

2