High power service manual for unit sizes 6x – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual
Page 132
Pin No. Schematic
Acronym
Function
Description
Reading Using a Digital Voltmeter
1
IU1
Current sensed,
U phase, not condi-
tioned
Approx 400 mv RMS
@100% load
.937 VACpeak
@ 165% of CT current rating. AC
waveform
@ output frequency of the frequency
converter.
2
IV1
Current sensed,
V phase, not conditioned
Approx 400 mv RMS
@100% load
.937 VACpeak
@ 165% of CT current rating. AC
waveform
@ output frequency of the frequency
converter.
3
IW1
Current sensed,
W phase, not condi-
tioned
Approx 400 mv RMS
@100% load
.937 VACpeak
@ 165% of CT current rating. AC
waveform
@ output frequency of the frequency
converter.
4
COMMON
Logic common
This common is for all signals.
5
AMBT
Ambient temp.
Used to control FAN high and low fan speeds.
1 VDC approximately equal to 25C
6
FANO
Control Card signal
Signal from the control card to turn the fans on and off. 0 VDC – ON command
5 VDC – OFF command
7
INRUSH
Control Card signal
Signal from the control card to start gating the SCR
front end
3.3 VDC – SCRs disabled
0 VDC – SCRs enabled
8
RL1
Control Card signal
Signal from Control Card to provide status of Relay 01 0 VDC – Relay active
0.7 VDC – inactive
9
Not
used
10
Not
used
11
VPOS
+18 VDC regulated sup-
ply +16.5 to 19.5 VDC
The red LED indicates voltage is present between VPOS
and VNEG terminals.
+18 VDC regulated supply +16.5 to 19.5 VDC
12
VNEG
-18 VDC regulated sup-
ply
-16.5 to 19.5 VDC
The red LED indicates voltage is present between VPOS
and VNEG terminals.
-18 VDC regulated supply
-16.5 to 19.5 VDC
13
DBGATE
Brake IGBT gate pulse
train
Varies w/ brake duty cycle
Voltage drops to zero when brake is turned off. Volt-
age increases to 4.04 VDC as brake duty cycle rea-
ches max.
14
BRT_ON
Brake IGBT 5V logic level
signal.
Varies w/ brake duty cycle
5.10 VDC level with the brake turned off. Voltage
decreases to zero as brake duty cycle reaches max.
15
Not
used
16
FAN_TST
Control signal for fans
Indicates Fan Test switch is activated to force the fans
on high
+5VDC – disabled
0VDC – fans on high
17
FAN_ON
Pulse train to gate SCR’s
for fan voltage control.
In sync with line freq.
7 trigger pulses at 3Khz
5VDC - fans off
High Power Service Manual for Unit Sizes 6x
131
10