6.2.11 6-** Analog In/Out
Parameter
Number
Parameter Description
Default Value
2 Setup
Change During
Operation
Conver-
sion
Index
Type
6 - 00
Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6 - 01
Live Zero TimeoutFunction
[0] Off
All set-ups
TRUE
-
Uint8
6 - 10
Terminal 53 Low Voltage
0.07 V
All set-ups
TRUE
-2
Uint16
6 - 11
Terminal 53 High Voltage
10 V
All set-ups
TRUE
-2
Uint16
6 - 12
Terminal 53 Low Current
0.14 mA
All set-ups
TRUE
-2
Uint16
6 - 13
Terminal 53 High Current
20 mA
All set-ups
TRUE
-2
Uint16
6 - 14
Terminal 53 Low Ref./Feedb. Value
0
All set-ups
TRUE
-3
Int32
6 - 15
Terminal 53 High Ref./Feedb. Value
50
All set-ups
TRUE
-3
Int32
6 - 16
Terminal 53 Filter Time Constant
0.01 s
All set-ups
TRUE
-2
Uint16
6 - 19
Terminal 53 mode
[0] Voltage mode
1 set-up
TRUE
-
Uint8
6 - 22
Terminal 60 Low Current
0.14 mA
All set-ups
TRUE
-2
Uint16
6 - 23
Terminal 60 High Current
20 mA
All set-ups
TRUE
-2
Uint16
6 - 24
Terminal 60 Low Ref./Feedb. Value
0
All set-ups
TRUE
-3
Int32
6 - 25
Terminal 60 High Ref./Feedb. Value
50
All set-ups
TRUE
-3
Int32
6 - 26
Terminal 60 Filter Time Constant
0.01 s
All set-ups
TRUE
-2
Uint16
6 - 81
Keypad potentiometer Low Ref.
0
All set-ups
TRUE
-3
Int32
6 - 82
Keypad potentiometer High Ref.
50
All set-ups
TRUE
-3
Int32
6 - 90
Terminal 42 Mode
[0] 0-20 mA
All set-ups
TRUE
-
Uint8
6 - 91
Terminal 42 Analog Output
[0] No operation
All set-ups
TRUE
-
Uint8
6 - 92
Terminal 42 Digital Output
[0] No operation
All set-ups
TRUE
-
Uint8
6 - 93
Terminal 42 Output Min Scale
0%
All set-ups
TRUE
-2
Uint16
6 - 94
Terminal 42 Output Max Scale
100%
All set-ups
TRUE
-2
Uint16
6.2.12 7-** Controllers
Parameter
Number
Parameter Description
Default Value
2 Setup
Change During
Operation
Conver-
sion
Index
Type
7 - 20
Process CL Feedback 1 Resource
[0] No function
All set-ups
TRUE
-
Uint8
7 - 30
Process PI Normal/ Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
7 - 31
Process PI Anti Windup
[1] Enabled
All set-ups
TRUE
-
Uint8
7 - 32
Process PI Start Speed
0 Hz
All set-ups
TRUE
-1
Uint16
7 - 33
Process PI Proportional Gain
0.01
All set-ups
TRUE
-2
Uint16
7 - 34
Process PI Integral Time
9999 s
All set-ups
TRUE
-2
Uint32
7 - 38
Process PI Feed Forward Factor
0%
All set-ups
TRUE
0
Uint16
7 - 39
On Reference Bandwidth
5%
All set-ups
TRUE
0
Uint8
6.2.13 8-** Comm. and Options
Parameter
Number
Parameter Description
Default Value
2 Setup
Change During
Operation
Conver-
sion
Index
Type
8 - 01
Control Site
[0] Digital and ctrl.word
All set-ups
TRUE
-
Uint8
8 - 02
Control Word Source
[1] GE Drive RS485
All set-ups
TRUE
-
Uint8
8 - 03
Control Word Timeout Time
1 s
1 set-up
TRUE
-1
Uint16
8 - 04
Control Word Timeout Function
[0] Off
1 set-up
TRUE
-
Uint8
8 - 06
Reset Control Word Timeout
[0] No function
1 set-up
TRUE
-
Uint8
8 - 30
Protocol
[0] GE Drive
1 set-up
TRUE
0
Uint8
8 - 31
Address
1
1 set-up
TRUE
0
Uint8
8 - 32
GE Drive Port Baud Rate
[2] 9600 Baud
1 set-up
TRUE
-
Uint8
8 - 33
GE Drive Port Parity
[0] Even Parity 1 Stop Bit
1 set-up
TRUE
-
Uint8
8 - 35
Minimum Response Delay
0.01 s
1 set-up
TRUE
-3
Uint16
8 - 36
Max Response Delay
5 s
1 set-up
TRUE
-3
Uint16
8 - 50
Coasting Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 51
Quick Stop Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 52
DC Brake Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 53
Start Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 54
Reversing Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 55
Set-up Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 56
Preset Reference Select
[3] Logic OR
All set-ups
TRUE
-
Uint8
8 - 94
Bus feedback 1
0
All set-ups
TRUE
0
Int16