Parameter
Number
Parameter Description
Default Value
2 Setup
Change During
Operation
Conver-
sion
Index
Type
3 - 00
Reference Range
[0] Min - Max
All set-ups
TRUE
-
Uint8
3 - 02
Minimum Reference
0
All set-ups
TRUE
-3
Int32
3 - 03
Maximum Reference
50
All set-ups
TRUE
-3
Int32
3 - 10
Preset Reference
0%
All set-ups
TRUE
-2
Int16
3 - 11
Jog Speed [Hz]
5 Hz
All set-ups
TRUE
-1
Uint16
3 - 12
Catch up/slow Down Value
0%
All set-ups
TRUE
-2
Int16
3 - 14
Preset Relative Reference
0%
All set-ups
TRUE
-2
Int16
3 - 15
Reference Resource 1
[1] Analog in 53
All set-ups
TRUE
-
Uint8
3 - 16
Reference Resource 2
[2] Analog in 60
All set-ups
TRUE
-
Uint8
3 - 17
Reference Resource 3
[11] Local bus reference
All set-ups
TRUE
-
Uint8
3 - 18
Relative Scaling Reference Re-
source
[0] No function
All set-ups
TRUE
-
Uint8
3 - 40
Accel/Decel 1 Pattern
[0] Linear
All set-ups
TRUE
-
Uint8
3 - 41
Accel Time 1
3 s
All set-ups
TRUE
-2
Uint32
3 - 42
Decel Time 1
3 s
All set-ups
TRUE
-2
Uint32
3 - 50
Accel/Decel 2 Pattern
[0] Linear
All set-ups
TRUE
-
Uint8
3 - 51
Accel Time 2
3 s
All set-ups
TRUE
-2
Uint32
3 - 52
Decel Time 2
3 s
All set-ups
TRUE
-2
Uint32
3 - 80
Jog Accel/Decel Time
3 s
All set-ups
TRUE
-2
Uint32
3 - 81
Quick Stop Ramp Time
3 s
1 set-up
TRUE
-2
Uint32
6.2.9 4-** Limits/Warnings
Parameter
Number
Parameter Description
Default Value
2 Setup
Change During
Operation
Conver-
sion
Index
Type
4 - 10
Reverse Lock
[2] Both directions
All set-ups
FALSE
-
Uint8
4 - 12
Motor Speed Low Limit [Hz]
0 Hz
All set-ups
FALSE
-1
Uint16
4 - 14
Motor Speed High Limit [Hz]
65 Hz
All set-ups
FALSE
-1
Uint16
4 - 16
Torque Limit Motor Mode
150%
All set-ups
TRUE
0
Uint16
4 - 17
Torque Limit Generator Mode
100%
All set-ups
TRUE
0
Uint16
4 - 50
Warning Current Low
0 A
All set-ups
TRUE
-2
Uint32
4 - 51
Warning Current High
26 A
All set-ups
TRUE
-2
Uint32
4 - 58
Missing Motor Phase Function
[1] On
All set-ups
FALSE
-
Uint8
4 - 61
Jump Frequency From [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
4 - 63
Jump Frequency To [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
6.2.10 5-** Digital In/Out
Parameter
Number
Parameter Description
Default Value
2 Setup
Change During
Operation
Conver-
sion
Index
Type
5 - 10
Terminal 18 Digital Input
[8] Start
All set-ups
TRUE
-
Uint8
5 - 11
Terminal 19 Digital Input
[10] Reversing
All set-ups
TRUE
-
Uint8
5 - 12
Terminal 27 Digital Input
[1] Reset
All set-ups
TRUE
-
Uint8
5 - 13
Terminal 29 Digital Input
[14] Jog
All set-ups
TRUE
-
Uint8
5 - 15
Terminal 33 Digital Input
[16] Preset ref bit 0
All set-ups
TRUE
-
Uint8
5 - 40
Function Relay
[0] No operation
All set-ups
TRUE
-
Uint8
5 - 55
Terminal 33 Low Frequency
20 Hz
All set-ups
TRUE
0
Uint16
5 - 56
Terminal 33 High Frequency
5000 Hz
All set-ups
TRUE
0
Uint16
5 - 57
Terminal 33 Low Ref./Feedb. Value
0
All set-ups
TRUE
-3
Int32
5 - 58
Terminal 33 High Ref./Feedb. Value
50
All set-ups
TRUE
-3
Int32