Powersolve C(AC) Series User Manual
22 kwatts, C (ac-dc) series, Ups/inverters
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: [email protected]
Specification
50-22 kWatts
•
CE Marked LVD & EMC
•
1-4 Outputs
•
5-400 Volts Output
•
Eurocassette or Wall Mount
•
Parallel Redundant Operation
•
Fully Wired Customised Racks
•
Power Factor Correction Modules
C (AC-DC) Series
Input
DC Input Voltage
• See Table
AC Input Voltage
• See Table
Input Frequency
• 47-440 Hz
No-Load Input Current • 3% of full load current typical
Inrush Current
• AC/DC limited by thermistor
DC/DC depends on impedance of supply
line, see List of Options for Option ‘I’
Earth Leakage
• <3.5 mA at 230 VAC, to EN60950
Output
DC Output Voltages
• See Table, for voltages above 250 VDC
contact Sales Office
Switch-On Time
• 100 ms typical C300-C4700,
500 ms typical C5600-C5800
Hold-Up Time
• AC/DC increases with input voltage
15 ms typical at 230 VAC
DC/DC depends on input voltage
(typical 2 ms at 12 VDC)
Line Regulation
• 0.1% (±10% change Vin)
Load Regulation
• 0.2% (10-90% load)
Transient Response
• 6% maximum deviation 2ms
C300-C4700, 10ms C5600-C 5800
recovery time to within 1% for load
change 20-100- 20% of full load
Ripple & Noise
• ≤1% +30 mV pk-pk
(0.5% typical lin. regulator auxiliary)
Overvoltage Protection • Standard on single output models &
main output on multi output units
Overload Protection
• Current limited at 105-110% of full load
Temperature Coefficient • 0.02%/°C typical
Remote Sensing
• Standard for main output
1
General
Efficiency at Full Load
• 60-95%, depending on model
Isolation
• EN60950 Class 1
Switching Frequency
• Approx. 33 KHz
MTBF
• AC/DC & DC/DC approx 130,000 hrs
at +25 °C
Connector
• H 15 DIN 41612 or studs for higher
current outputs C300-C4700,
studs only for C5600-C5800
Environmental
Operating Temperature • -20 °C to +75 °C, derate from +55 °C
at 2.5%/°C (Optional -40 °C to +75 °C)
Storage Temperature
• -40 °C to +85 °C
Relative Humidity
• 5-95%, non-condensing
EMC & Safety
RFI-Interference
• VDE 0878, EN 55022, Level A
Construction (Safety)
• EN60950 Class 1
Creepage Distance
• VDE 0110, 4 mm
Air Distance
• VDE 0110, 3 mm
High-Energy
• ENV 50142, Level 3
Pulses/Surges
Spike/Bursts
• IEC 1000-4-4, Level 3
UPS/INVERTERS