Specification
1.5-6.0 kVA UPS/INVERTERS
•
External Maintenence Bypass Switch
•
Single & Dual Input
•
Electric Interlock
•
Rack Mount / Wall Mounting Format
•
115 VAC & 230 VAC Versions
Xi EMBS Series
Input
Input Voltage
• 115 V single phase, 80-138 V
230 V single phase, 176-276 V
Output
Output Voltage
• 115 V single phase, 80-138 V
230 V single phase, 176-276 V
Output Regulation
• See Output Characteristics Table
General
Dimensions
• See Output Characteristics Table
IP Rating
• IP30
Connector Type
• Contact Sales Team
Environmental
Operating Temperature • 0 ˚C to +40 ˚C
Storage Temperature
• -10 ˚C to +85 ˚C
Operating Humidity
• <0-95% RH, non-condensing
Storage Humidity
• <0-95% RH, non-condensing
Operating Altitude
• 1000 metres
Shock & Vibration
• <2 g
EMC & Safety
Safety Standards
• EN60947 1999 low voltage switchgear
& control gear
Product Description
The External Maintenance Bypass Switch (EMBS) permits the maintenance or repair of a UPS system by providing a simple but efficient means of
temporarily isolating/removing the UPS from the power circuit without interrupting power to the critical load.
All EMBS panels supplied by Powersolve are fitted with an electrical interlock to prevent the maintenance supply being accidentally
connected in parallel with the UPS output. Service personnel are provided with a key operated over-ride switch to allow the maintenance bypass
breaker to be closed once the UPS has been transferred to internal bypassmode, during normal maintenance of the system.