AC Input
85...264Vac , 47...63Hz , 90…350Vdc
AC Input Rating
100...240Vac , 115Vac <2.6A 230Vac <1.3A
DC Voltage Adjust
9...18Vdc(12V)
18..30Vdc(24V) 30...43Vdc(36V) 43...53Vdc(48V) 53...72Vdc(60V) 68...86Vdc(72V)
Over Voltage
Protection
21Vdc
35Vdc
50Vdc
60Vdc
84Vdc
97Vdc
Rated Current 60°C 15.0A (12Vdc)
10.0A (24Vdc)
6.7A (36Vdc)
5.0A (48Vdc)
4.0A (60Vdc)
3.3A (72Vdc)
Rated Current 40°C 19.0A (12Vdc)
13.0A (24Vdc)
8.7A (36Vdc)
6.5A (48Vdc)
5.2A (60Vdc)
4.3A (72Vdc)
Boost 60s/60°C
18.0A (12Vdc)
12.0A (24Vdc)
8.0A (36Vdc)
6.0A (48Vdc)
4.8A (60Vdc)
4.0A (72Vdc)
Ripple
mVpp/230Vac
30 (20MHz)
30 (20MHz)
60 (20MHz)
50 (20MHz)
50 (20MHz)
60mV
Load regulation 0-
100%
±0.5%
±0.2%
±0.2%
±0.2%
±0.2%
±0.2%
Tolerance Ua adjusted
± 0.5%
Transient Time
<1ms (10-100% , 100-10%)
Minimum Load
0 A
Efficiency
91.5% typical
Load Protection
1,2x I
rated
, auto recovery
Short Circuit Protection
Yes
Temperature Controlled
Yes (see right graph)
Hold Up Time
> 40ms (100...230Vac input)
Inrush Current
< 7A (230Vac), active limiter
Softstart
50ms typical
Temperature Control:
If the ambient temperature (ta)
≤
40°C the HPW provides I/Boost
continuously and if ta
≤
60°C Irated is provided continuously. If ta >60°C
derating continuously lowers Vout 2,5%/Kelvin. If ta >70°C (or thermal
overload occures) the HPW shuts down. It auto-recovers when the
device cools down to approved operation conditions.
Cooling
Natural convection
Ambient Temperature
- 25°C…+70°C
Storage Temperature
- 40°C…+85°C
EMI
EN55022 class B / EN61000-3-2
EMS
EN61000-6-2,3 active PFC
Safety
cUL60950 , (IEC)EN60950-1
Safety class 1(A)
VDE0805, VDE0100
Air & Surface Leakage Paths
> 8mm
Input/Output
Galvanic insulated
DC Fail Relay (galv. insulated)
≤
48Vdc/500mA ,
≤
30Vac/500mA
Relative Humidity
95% (25°C) non-condensing
Pollution Degree
2 (EN50178)
Climatic Class
3k3 (EN60721)
MTBF (IEC61709)
500000h
Dimensions (HxWxD)
130x75x115mm
Weight
1200g
Connectors (AC & DC)
(see page 4)
AWG20...AWG6
IEC60664-1, IEC61984
Specification:
The HPW02401 DIN Rail power supply series is designed for worldwide electronics applications like machine building, railway,
military and factory automation. Its regulated DC output with ripple/noise lower than 30mVpp and its high efficiency of 91.5%
makes the HPW robust, economical and reliable. Camtec power supplies are tradionally made with high end low ESR
electrolytic output capacitors with withstanding +125°C temperature. Our capacities are rather designed over for longer
lifetime and longer hold up times. The power boost of the HPW starts DC-loads and DC-motors reliable. The built in function
diagnostics detects malefunctions. The galvanic insulated DC fail relay and remote on/off provides full control over the power
supply unit. The HPW is short circuit and zero load stability protected. It is protected against high transient and provides very
good interference resistance. Equal types of the HPW02401 can be operated in parallel or in series connection. We use IP20
stabile aluminium hausings with vantilation slots in accordance to the demanding VDE norms.
The design meets EN (IEC)60950-1 and low voltage directive EN55022 Class B.
Block Diagram
1)
Transient suppressor (VDR)
2)
AC fuse
3)
Electronic Inrush Current Limiter
4)
Load Capacitor C
5)
Rectifier & Active PFC
P Potentiometer
Complex sane filter technology using 2 varistors, noise
suppression chokes and X1 capacitors, apply major transient
resistance to the input filter. The synchron rectifier increases the
efficiency of the APW crucial. Compared to diode rectifying the
power dissipation drops to a minimum. The emission is much
lower to result in a longer lifetime of the APW power supply.
Overload: If 0.9xVout applies to the outputs, the red LED lights and
the DC-OK-Relay (Re) drops (control message). The green DC-OK
LED is off.
For further
derating
information
see table
page 3