beautypg.com

3 trouble shooting in else cases – PowerWalker VFI 6000T LCD User Manual

Page 53

background image

50

7.3 Trouble Shooting In Else Cases

Problem

Possible cause

Remedy

No indication, no

warning tone even

though system is

connected to mains

power supply

No input voltage

Check the building wiring and

input cable.

Check if the input breaker is

closed.

BYPASS LED light up

even though the power

supply is available

Inverter not switched

on

Press On-Switch “I” to turn on

UPS.

BATTERY LED lights

up, and audible alarm

sounding every 1 beep

in every 4 seconds

Input voltage and/or

frequency are out of

tolerance

Check input power source.

Check the building wiring and

input cable.

Check if the input breaker is

closed.

Emergency supply

period shorter than

nominal value

Batteries not fully

charged / batteries

defect

Charge the batteries for at least

12 hours and then check

capacity.

Please have the following information at hand before calling the

After-Sales Service Department:

1. Model number, serial number

2. Date on which the problem occurred

3. LCD/LED display information, Buzzer alarm status

4. Mains power condition, load type and capacity, environment temperature,

ventilation condition

5. The information (battery capacity, quantity) of external battery pack if the

UPS is “S” model

6. Other information for complete description of the problem