8) Connect other input and output wires to the corresponding input

and output terminals according to the following diagram.

9) It is requested to use the accessorial terminal splices which can

be compacted on the wires tightly, to ensure the connection

between the wires and the terminal block is reliable.

Fig. 4-7 Input and output Terminal Block wiring diagram

Notes: 1) If the UPS is used in single mode, JP1 and JP2 must be

connected. If the UPS is used in parallel mode, the Jumper between

JP1 and JP2 must be removed.

2) Battery+/- connection is only for “S” model.

10) Install an output breaker between the output terminal of UPS

and the load, and the breaker should with leakage current

protective function if necessary.

11) Turn off all the loads first before connecting the load with the

UPS, then perform the connection and finally turn on the loads

one by one.

12) After completing the installation, check all the wires is

connected correctly and tightly.

13) Suggest charging the batteries for 8 hours before use. After

installation, turn on the mains power switch and turn the input

breaker in the “ON” position, the UPS will charge the batteries

automatically. It can also use the UPS immediately without

charging the batteries, but the backup time may be less than the

standard value.