2 trouble shooting according to fault indication – PowerWalker VFI 6000T LCD User Manual
Page 52
49
7.2 Trouble Shooting According To Fault Indication
Problem Displayed
Possible cause
Remedy
Inv Overload Fault
Overload
Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Byp Overload Fault
Overload
Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Output Short Circuit
Output short circuit
Remove all the loads. Turn off
the UPS.
Check if UPS output and loads
is short circuit.
Ensure short circuit is removed
before turning on again.
Heatsink Over
Temperature Fault
Inside temperature of
UPS is too high
Check the ventilation of UPS
and the ambient temperature.
Bus Over Voltage
UPS internal fault
Consult dealer.
Bus Under Voltage
UPS internal fault
Consult dealer.
Bus Unbalance
UPS internal fault
Consult dealer.
Bus short
UPS internal fault
Consult dealer.
Bus Softstart Fail
UPS internal fault
Consult dealer.
Inv Over Voltage
UPS internal fault
Consult dealer.
Inv Under Voltage
UPS internal fault
Consult dealer.
Inv Softstart Fail
UPS internal fault
Consult dealer.
Negative Power Fault
The load is pure inductive
and capacitive
Remove some non-critical
loads.
Bypass supplies the load first,
ensure there is no overload,
then turn on UPS.
Cable male and female
Loss fault
The parallel cable is
disconnected
Check the parallel cable.
Fan lock fault
Fan blocked or
disconnected over time
Check the fan status
Back Feed
Output voltage is
returned to input
Consult dealer