PowerWalker VFI 6000T LCD User Manual

Page 45

background image

42

6.3.2 Parallel installation and operation

How to install a new parallel UPS system:

1) Before installing a new parallel UPS system, user need to

prepare the input and output wires, the output breaker, and the

parallel cable.

2) Users need to use a standard 25-pin communication cable,

which should have 25 cores, corresponding stitches and shield,

as the UPS parallel cable. The length of the parallel cable is

appropriate to be less than 3m.

3) Remove the cover plate of the parallel port on the UPS,

connect each UPS one by one with the parallel cable, and

re-screw the Parallel port cover which is supplied in the

accessories.

4) Strictly follow the chapter of 4, the wiring requirement of single

UPS to perform the wiring of each UPS.

5) Connect the output wires of each UPS to an output breaker

panel.

6) Disconnect the Jumper on JP1 and JP2 of the terminal block

first, and connect each output breaker to a main output breaker

and then to the loads.

7) Each UPS need an independent battery pack.

8) Please refer to the wiring diagram in the following diagram.

9) The distance between the UPSs in parallel and the breaker

panel is required to be less than 20 meters. The difference

between the wires of input and output of the UPSs is required to

be less than 20%.