Outstanding adaptability to the worst mains input condition.

Extra wide input voltage, frequency range and waveform, avoid

excessive dissipating limited battery energy.

Internal charger could be up to 4Amps to decrease recharging

time of battery. Optional external large charging current charger

which is up to 12Amps could be supplied.

N+X parallel redundancy to increase the reliability and flexibility.

Number of parallel operating UPS is up to 4.

HE mode with high efficiency

0.96, save power expense for

user.

Input or output ISO transformer compatibility.

Start-able without battery.

3.2 Electrical specifications

INPUT

Model No.

PowerWalker

VFI 6000T LCD (L)

PowerWalker

VFI 10000T LCD (L)

Phase

Single

Voltage

176~276VAC

Frequency

(45~55)/(54~66) Hz

Current(A)*

25.8

43.0

THDI

< 5% @ full load

Power Factor

0.99 @ full load

*Rated current while input rated voltage is 230VAC

OUTPUT

Model No.

PowerWalker

VFI 6000T LCD (L)

PowerWalker

VFI 10000T LCD (L)

Power rating

6kVA/5.4kW

10kVA/9kW

Voltage

208*/220/230/240×

1

1%

VAC

Frequency

50/60×

1±0.05

Hz (Battery mode)