beautypg.com

PowerWalker VFI 6000T LCD User Manual

Page 49

background image

46

automatically, set the own maintenance switch of each UPS

from “UPS” to “BPS”.

3)

Set the main maintenance switch or static switch from “UPS” to

“BPS”, switch off the main output breaker and the main input

breaker, and the UPSs would shut down.

4)

Ensure the UPSs shut down totally, remove the wanted UPS

and reinstall the new UPS parallel system by following step 1)

to 9) of last chapter - “install a new parallel UPS system”.

5)

If the removed UPS or the remained UPS will be used in a

stand-alone mode, then JP1 and JP2 on the terminal block

should be connected with a short connection wire.

6)

Switch on the main input breaker and the main output breaker,

and set the main maintenance switch or static switch from

“BPS” to “UPS”, then set the UPS own maintenance switch

from “BPS” to “UPS” and screw the maintenance cover plate

back again. Press the

button of one UPS, each UPS would

start to turn on, after turning on, the UPSs should work parallel

in the Line mode.