beautypg.com

PowerWalker VFI 6000T LCD User Manual

Page 47

background image

44

Fig. 6-2 Parallel System Installation Diagram

10) Do not switch on the output breaker of each UPS, switch on the

input breaker of the each UPS, the UPS should work in bypass

with output, observe their display to check if there are any

warning or fault information, measure the output voltage of

each UPS separately to check if the voltage difference between

them is less than 1V. If the difference is more than 1V, check

the wiring.

11) Press the

button of one UPS, each UPS would start to turn

on, all the UPSs would transfer to the INV mode together.

Measure the output voltage of each UPS separately to check if

the voltage difference between them is less than 0.5V. If the

difference is more than 0.5V, the UPSs need to be regulated.

12) Press the

button of one UPS, each UPS would start to turn

off and transfer to the Bypass mode, switch on the output

breaker of each UPS to parallel all the output of UPSs together.