13) Press the

button of one UPS, each UPS would start to turn

on, after turning on, the UPSs should work parallel in the Line

mode.

How to join a new UPS to a parallel system:

1)

First the parallel system must be installed one main

maintenance mechanical switch or static switch.

2)

Regulate the output voltage of the new UPS

separately: check

if the output voltage difference between the new UPS and the

parallel system is less than 0.5V.

3)

Ensure the bypass of the parallel system is normal and the

bypass setting is “enable”, remove the cover plate of

maintenance switch on the rear panel of each UPS, the UPS

system would transfer to bypass automatically, set the own

maintenance switch of each UPS from “UPS” to “BPS”.

4)

Set the main maintenance switch or static switch from “UPS” to

“BPS”, switch off the main output breaker and the main input

breaker, the UPSs would shut down.

5)

Ensure the UPSs shut down totally, add the new UPS and

reinstall the new UPS parallel system by following step 1) to 9)

of last chapter - “install a new parallel UPS system”.

6)

Switch on the main input breaker and the main output breaker,

and set the main maintenance switch or static switch from

“BPS” to “UPS”, then set the UPS own maintenance switch

from “BPS” to “UPS” and screw the maintenance cover plate

back again. Press the

button of one UPS, each UPS would

start to turn on, after turning on, the UPSs should work parallel

in the Line mode.

How to remove a single UPS from a parallel system:

1)

First the parallel system must be installed one main

maintenance mechanical switch or static switch.

2)

Ensure the bypass is normal and the bypass setting is “enable”,

remove the cover plate of maintenance switch on the rear panel

of each UPS, the UPS system would transfer to bypass