5.4.5 The control menu
By pressing
on the menu of “Control”, the display would enter
the next control menu tree.
1) Single UPS turn off: is one command to turn off one UPS which
is operated currently in a parallel system, and other UPSs
continue working to supply the load in the parallel system.
2) Single UPS battery test: is one command to control one UPS
which is operated currently in a parallel system to do the battery
test singly, and other UPSs do not do the battery test.
3) Parallel UPS battery test: is one command to control all UPS in
a parallel system to do the battery test at the same time.
4) Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO
connector should be opened, and enter this menu to clear EPO
status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
5) Reset fault status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu
to reset error status, then UPS would stop alarm and recover to
Bypass mode. And the reason of fault should be checked and
deleted before UPS is turned on again by manual operation.
6) Restore factory settings: all the settings would be recover to
default factory settings. It could only be done in Bypass mode.