3 operating environment – PowerWalker VFI 6000T LCD User Manual
Page 11
8
Wave form
sinusoidal
Load type
PF 0.5~1, lagging
THDV
< 2% @ full linear load
<5% @ full non linear load
Overload
In Line mode**:
10 min 105~125%
1 min 125~150%
10 s >150%
100 ms >170%
In Battery mode:
2 min 105~125%
30 s 125~150%
100 ms >150%
*The load capacity would be derated to 90% automatically when the output
voltage is adjusted to 208VAC.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
BATTERIES
Model No.
PowerWalker
VFI 6000T LCD
PowerWalker
VFI 10000T LCD
Internal BAT
number and type
20×12V 7Ah
20×12V 9Ah
Current of external
BAT pack
32Amax
50Amax
3.3 Operating Environment
Operating Temperature
0
o
C to 45
o
C
Operating humidity
< 95%
Altitude
< 1000m*
Storage temperature
-15
o
C to 50
o
C
*The load capacity should be derated 1% every 100m heightened on the basis
of 1000m.