28

5.3.3 Turning off UPS with mains

1) To turn off the inverter of UPS by pressing

button

continuously for more than 3s and the buzzer will beep for 3s.

The UPS will turn into Bypass mode at once.

2) When completing the above action, UPS output voltage is still

present. In order to cut off the UPS output, simply cut off the

mains power supply. A few seconds later, LCD display shuts

down and no output voltage is available from the UPS output

terminal.

5.3.4 Turning off UPS without mains

1) To power off the UPS by pressing

button continuously for

more than 3s, and the buzzer will beep 3s. The UPS will cut off

the output at once.

2) A few seconds later, LCD shuts down and no voltage is

available from the UPS output.

5.4 LCD Operation

Except the default UPS status summary screen, the user could get

more useful information about UPS current status, detailed various

measurements, old events which ever occurred, UPS own

identification, and could change the settings to fit the user own

requirements, optimize the function of UPS.

5.4.1 The main menu

In the default UPS status summary screen, when pressing

or

<1s, the detailed information about alarm, the parallel system,

battery would be shown.

In the default UPS status summary screen, when pressing

>1s,

the display would enter main menu tree.

The main menu tree includes six branches: UPS status menu, event

log menu, measurement menu, control menu, identification menu,

setting menu.