4.3.2 Installation

Use cable cross section and protective device specification

Model

PowerWalker VFI

6000T LCD (L)

PowerWalker VFI

10000T LCD (L)

Protective earthing conductor

Min cross section

6mm

2

(8AWG)

10 mm

2

(6AWG)

Input L, N, G

Min conductor cross section

6mm

2

(8AWG)

10 mm

2

(6AWG)

Input breaker

40A/250VAC

63A/250VAC

Output L,N,

Min conductor cross section

6mm

2

(8AWG)

10 mm

2

(6AWG)

External Battery Cabinet

Positive Pole(+), Negative pole(-),

Neutral Pole

Min conductor cross section

6mm

2

(8AWG)

10 mm

2

(6AWG)

External Battery Cabinet Fuse

in Positive Pole(+), Negative pole(-),

Neutral Pole

30A/240VDC

60A/240VDC

External Battery Cabinet Breaker

in Positive Pole(+), Negative pole(-),

Neutral Pole

32A/240VDC

50A/240VDC

Torque for fixing above terminals

3.95~4.97Nm

(35~44 1b in)

1)

It is suggested to install an external isolating device against

current backfeed between Mains input and UPS (see Fig.4-6).

After the device is installed, it must add a warning label with the

following wording or the equivalent on the external AC contactor:

RISK OF VOLTAGE BACKFEED. Isolate the UPS before

operating on this circuit, then check for hazardous voltage

between all terminals.

For safety, please cut off the mains power switch before
installation!