PowerWalker VFI 6000T LCD User Manual
Page 41
38
Table 5-4
Submenu item
Optional Values
Default value
User password
enabled/disabled
disabled
Audio alarm
enabled/disabled
enabled
Rated output voltage
208/220/230/240V
230V
Output frequency
autosensing/50/60Hz
autosensing
Power strategy**
normal/high efficiency/ converter normal
DC start
enabled/disabled
enabled
Site wiring fault alarm
enabled/disabled
enabled
Ambient
temperature
warning
enabled/disabled
enabled
Automatic
battery
tests
period
0-31days
7days
Auto Restart
enabled/disabled
enabled
Automatic overload restart
enabled/disabled
enabled
AutoBypass
enabled/disabled
enabled
Short circuit clearance
enabled/disabled
disabled
Bypass voltage low limit
110~215V
176V
Bypass voltage high limit
245~276V
264V
Bypass frequency low limit
1%~10%
10%
Bypass frequency high limit
1%~10%
10%
HE voltage low limit
1%~10%
5%
HE voltage high limit
1%~10%
5%
HE frequency low limit
1%~10%
5%
HE frequency high limit
1%~10%
5%
Battery quantity***
19/20/21
20
Set running time
Day:hour:minute:second
0000:0000:00~9999:23:59:59
Running time
LCD contrast
-5~+5
0
*Password is USER when enabled.
**Read the chapter of 6.1 and 6.2, before using high efficiency or converter function.
***Ensure the real battery quantity is same as the setting, or the batteries would be
damaged
permanently.