5 exchanging the electronics module, 6 software update, 7 how to proceed in case of repair – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Approval according to LPR radio standard User Manual
Page 58
Since we offer this service worldwide, the support is in the English
language. The service itself is free of charge, the only costs involved
are the normal call charges.
8
.5 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module with
respective Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The
electronics modules are adapted to the respective sensor and differ in
signal output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
l
In the factory
l
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside of
the housing as well as on the delivery note.
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Electronics
module").
8
.6 Software update
The following components are required to update the sensor software:
l
Sensor
l
Voltage supply
l
Interface adapter VEGACONNECT 4
l
PC with PACTware
l
Current sensor software as file
Caution:
Note that due to a software update you can lose approvals.
You can find the actual sensor software as well as detailed information
of the procedure on our home page under "www.vega.com/down-
loads" on "Software".
8
.7 How to proceed in case of repair
If a repair is necessary, please proceed as follows:
58
VEGAPULS
62 • Approval according to LPR radio standard
8 Diagnosis, Asset Management and service
41722
-EN
-120706