beautypg.com

1 general information, 2 setting of the device trend – VEGA RS232_Ethernet connection User Manual

Page 59

background image

59

12 Device trend/Data logger (only VEGAMET/VEGASCAN)

RS232/Ethernet connection • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30325-EN-130701

12 Device trend/Data logger (only VEGAMET/

VEGASCAN)

12.1 General information

With the device recording the measured values of a VEGA instrument

can be monitored. There are two options for trend recording:

The data are saved over a certain period in the VEGA instrument

and can be read out again later on. Via PACTware and DTM different

recording conditions can be set and the process can be started or

stopped. The max. recording period is limited by the memory of the

signal conditioning instrument. The max. recording period differs de-

pending on the recording type (interval or measured value difference).
When recording with interval, a maximum of 200 000 measured val-

ues can be recorded, when recording with measured value difference,

the maximum is reduced to 140 000. If a measured value is saved

every minute, a period of e.g. 138 days results (with measured value

difference). If more than one curve is recorded, this period is reduced

accordingly.
Note:

The recorded data are written in a period of two to five minutes from

the internal RAM to a flash disk. In case of voltage failure, recordings

of the last minutes can get lost.

The data are only saved on the PC during an online connection with

PACTware and DTM. The max. recording period is limited only by the

storage space on the hard disc.

12.2 Setting of the device trend

The settings are carried out in the DTM under the menu item "Diag-

nostics - Device trend - Settings". Depending on the device, up to 15

curves are available (3x with VEGAMET or 15x with VEGASCAN). If

required, these curves are activated or deactivated/deleted on this

side. By pushing the button "Add", an installation assistant for creating

the selected curve is started. The following settings are carried out

step-by-step:

In the first step you have to select the requested measurement loop

and the measured value.

Here you set the requested recording interval. The following options

are possible:

"In time interval": Recording is carried out in certain adjustable

time intervals

"With measured value difference": Recording is carried out meas-

ured value dependent with adjustable measured value difference

A combination of the two recording modes is also possible.

Device trend

DTM trend

Measurement loop/Meas-

ured value

Recording mode