9 Measured value transmission to a WEB-VV server
RS232/Ethernet connection • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30325-EN-130701
•
To keep transmission costs low, we recommend using a pure data
rate (M2M) with low data block rounding (1 kB)
Start PACTware and make a connection to the signal conditioning
instrument. Select the menu item "Instrument settings - LAN/Internet".
Carry out the following steps as shown in the following illustrations.
Give every signal conditioning instrument a unique IP address from
the address range of the MoRoS (192.168.1. xxx); the address of
the MoRoS itself (192.168.1.1) may be not used. The subnet mask
remains unchanged (255.255.255.0). Type in the IP address of the
MoRoS under Standard gateway.
Fig. 19: IP addressing
Enter the IP address of the MoRoS under "Instrument settings - DNS
Server".
Fig. 20: DNS addressing
The access data of the mobile telecommunications provider must
be written into the MoRoS. You can find the procedure in chapter
"Commissioning the MoRoS" as well as in the operating instructions
manual.
Define a WEB-VV event as described in chapter "Set up measured
value transmission".
IP addressing
DNS addressing
MoRoS setup
Measured value transmis-
sion