4 technical data – VEGA VEGAMET 614 User Manual
Page 6
6
VEGAMET 614
1.4 Technical data
Power supply
Operating voltage
U
nom
= 20 … 250 V AC, 50/60 Hz
= 20 … 72 V DC
Power consumption
approx. 10 VA or approx. 4 W
Meas. data input
Number
1 input
Input type
active two-wire input, analogue (sensor is
powered by VEGAMET)
Range
4 … 20 mA
Applicable sensors (loop powered)
capacitive electrodes, pressure transmitters,
process pressure transmitters, differential
pressure transmitters,
ultrasonic sensor (4 … 20 mA sensor),
radar sensor (4 … 20 mA sensor)
Voltage
- at 4 mA
approx. 19.5 V DC
- at 20 mA
approx. 16 V DC
Current limitation
at approx. 26 mA, short-circuit-proof
Detection line break
< 3.6 mA
Detection short-circuit
> 21 mA
Min. adjustment delta
2 % of the entered sensor values
Connection cable
2-wire standard cable (screening
recommended)
max. resistance per wire
35
Ω
Resolution
1 µA
Linearity error
0.025 % at 4 … 20 mA
Temperature error
0.04 %/10 K at 4 … 20 mA
Current output
Number
1 output
Function
analogue output of the processing results
Range
adjustable between 0 … 20 mA
Load
max. 500
Ω
Resolution
1 µA
Linearity error
0.05 % (relating to 20 mA)
Temperature error
0.05 %/10 K (relating to 20 mA)
Voltage output
Number
1 output
Function
analogue output of the processing results
Range
adjustable between 0 … 10 V
Current
max. 1 mA
Resolution
0.5 mV
Linearity error
0.05 % (relating to 10 V)
Temperature error
0.06 %/10 K (relating to 10 V)
Product description