beautypg.com

3 electrical connection, 1 connection instructions, 3 wiring plan – VEGA VEGAMET 614 User Manual

Page 12

background image

12

VEGAMET 614

17 18 19 20 21 22

9

10

11 12

1

2

3

4

23 24 25 26 27 28

13 14

15 16

5

6

7

8

L1 N

+ -

+ -

+ -

+ -

+ -

Electrical connection

Ex version

Before connecting Ex certified instruments,
please note the instructions in the attached
official documents as well as the valid installa-
tion regulations. Make sure that the Ex sepa-
rating chamber is plugged in on the left
instrument side before setup (see illustration
Coding).

3.3 Wiring plan

Fail
safe
relay

Level
relay 1

Level
relay 2

Power supply

Sensor

DISBUS
output

Current
output

Voltage output

The connections "9, 10, 15, 16, 17 and 18“ can be
connected with the supplied jumpers to neighbouring
series 600 signal conditioning instruments.

3.1 Connection instructions

Note the following instructions for electrical
connection:
- The connection must be made acc. to the

local installation standards (e.g. in Ger-
many acc. to the VDE-regulations).

- The wiring between VEGAMET 614 and

sensor can be made with standard two-
wire cable.

- If strong electromagnetic interferences are

expected, we recommend the use of
screened cable. The screening must be
earthed on both ends.

- The line resistances stated in the technical

data must not be exceeded.

- If overvoltages are expected, we recom-

mend a sensor electronics with integrated
overvoltage protection or the installation of
VEGA overvoltage arresters.

3.2 Connection instructions for

Ex approved applications

When wiring between VEGAMET 614 Ex and
an explosion protected sensor, the installation
rules, in Germany acc. to VDE 165 and the
EC type approval certificate, must be ob-
served. The official documents are supplied
with the respective instrument.

3 Electrical connection