6 parameter adjustment of outputs, Current outputs/volt outputs, Settings in the "extended menu – VEGA VEGAMET 614 User Manual

Page 32

background image

32

VEGAMET 614

Settings in the "Extended menu“

7.6 Parameter adjustment of outputs

Current outputs/Volt outputs

Param.
TAG-
No. 1

Adjust-
ment

Signal
condit-
ioning

Out-
puts

Cur-
rent
out-
puts

Volt
out-
puts

Cur-
rent
output
1

Volt
output
1

prop.
to

Per-
cent

Unit

0,0%

prop.
to

Per-
cent

Unit

0,0%

TAG -
No. 1
%
xx,x

Volume

TARE%

Volume

TARE%

Volt
output

0/10V

Failure
mode

0V

Volt
limita-
tion

on

Volt
at
0%

0,000

Volt
at
100%

10,000

10/2V
10/0V
2/10V
free

0,0
..10,0

0,0
..10,0

11V
- -
0%
100%

off

Current
output

Failure
mode

0mA

Current
limita-
tion

on

Cur-
rent
at 0%

4,000

Current
at
100%

20,000

0/20mA
20/4mA
20/0mA
free

0,0
..20,0

0,0
..20,0

22mA
- -
0%
100%

off

In the menu item "

prop. to

“, you can choose

between percent and volume. "Prop. to vol-
ume“ is then useful when under "Signal condi-
tioning - Linearisation curves“, for example, a
spherical tank or an individually defined
linearisation curve is selected. The output
current or the output voltage is then propor-
tional to the volume of the tank contents.

Unit:

Selection list dependent on the choice in the
previous menu item "prop. to“ (see chapter "8
Measured quantity and units“).

Volt output/Current output:

If "free“ is chosen, the following (light grey)
menu items appear:

- Volt at 0 %/100 %:

Individual voltage values between 0 V and
+10 V can be set.

- Current at 0 %/100 %:

Individual current values between 0 mA
and +20 mA can be set.

Failure mode:

The height of the output current/output volt-
age in case of failure is determined. If "--“ is
chosen, the actual value is maintained.

Volt limitation/Current limitation on:

Voltage/current remain within the values
which are given in the menu item "Voltage
output/current output".