VEGA VEGAMET 614 User Manual
Page 47
VEGAMET 614
47
E035
Instrument error. A serious error was detected in the instrument (check sum
error in EPROM). Disconnect voltage and then connect again (cold start). If the
error is not eliminated, please contact your VEGA agency.
E050
Remote VEGAMET not found. The VEGAMET from which a measured value is
expected cannot be found.
Reasons:
- the remote VEGAMET is not connected
- no VEGAMET with this instrument address connected
- line break (DISBUS)
- short-circuit (DISBUS)
- the remote VEGAMET is defective
- interfered communication (DISBUS)
Also possible:
- failure in the DISBUS transmitter/receiver part of VEGAMET
Please check the instrument address on both VEGAMETs, the connection
cable, the remote VEGAMET and, if necessary, this VEGAMET.
E051
Failure during transmission of measured values via DISBUS. It is not possible
to receive a valid measured value via DISBUS from the remote VEGAMET; the
communication with the remote VEGAMET, however, is okay.
Reason:
- failure on remote VEGAMET
- the input of the remote VEGAMET, which should be transmitted to, is not yet
configured
Please check the remote VEGAMET and, if necessary, its input configuration.
E052
The input number of the VEGAMET from which a measured value is expected
has not yet been assigned.
E053
Span of the sensor characteristics values too small. The sensor characteristics
values are too close together or are identical.
E054
Sensor characteristics values reversed. The min. sensor characteristics value
is higher than the max. sensor characteristics value.
E060
Span of the current output values too small. The values for the current output
are too close together or are identical. Please check the adjustment of the
current output.
E061
Span of the voltage output values too small. The values for the voltage output
are too close together or are identical. Please check the adjustment of the
voltage output.
E063
Incorrect sensor characteristics values. Please check the sensor characteris-
tics values
E102
A reset of the configuration was carried out on this VEGAMET via the key-
board.
Error code
Meaning
Diagnosis