VEGAMET 614

6.4 Scaling

Settings in the "Reduced menu“

The adjustments under scaling determine
which number values and which unit will be
actually displayed on the measured value
indication (upper menu item). In the menu
items "0 % corresponds…“ and "100 % cor-
responds…“ you can enter with [+] or [–]
and [OK] values which should be displayed
at 0 % and at 100 % filling. In the menu item
"Decimal point…“ you determine the position
of the decimal point. In the next menu item
"prop. to…“ you can select from a list of pa-
rameters: percent, mass, volume, pressure
etc. After pushing [+] or [–] save with [OK].
According to this adjustment, the menu item
"Unit…“ provides a new choice, e.g. m, dm,
cm, mm, ft, yd and in, if you have selected
the parameter "Height“ (compare chapter "8
Measured quantity and units“).

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Signal
condit-
ioning

Scal-
ing

Integr
ation
time s

0

Unit

– –

prop.
to

unde
fined

Deci-
mal
point

888,8

100%
corres
ponds

1000

0%
corres
ponds

0

Meas.
value
indication

Scaling example

You have a raised tank and you want the
level to be indicated in meters with three
digits after the decimal point.

Enter the number 1500 (with keys
[+], [–] and [OK]) in this menu item.
This corresponds to the level at 0 %
(if you want to have a lower resolution

of the meas. value indication, you can also
enter 150 or 15).

Enter the number 4500 (with keys
[+], [–] and [OK]) in this menu item.
This corresponds to the level at
100 %.

Adjust the decimal point as shown
(with keys [+], [–] and [OK]).

0%
corres
ponds

1500

100%
corres
ponds

4500

Deci-
mal
point

8,888

100 %

0 %

h=1.5 m

h=4.5 m

2.341 m