Settings in the "Extended menu“
7.5 Conditioning
The menu items "
Scaling
“ and "
Integration
time
“ corresponds to the menu items in the
"reduced menu“ (see appropriate chapter).
The menu items "
Density…
“ or "
DK value…
“
are displayed as options when under "Con-
figuration measurement loop“ the appropriate
sensor type has been selected. The density
or DK value must, before adjustment with
medium, be so adjusted that it corresponds
to the value of the medium (water has a den-
sity of 1.0 kg/dm
3
and a dielectric value of
81.00).
The following linearisation curves are avail-
able:
- linear (factory setting)
- horiz. cylindrical tank
- spherical tank
- Lin-curve 1
- Lin-curve 2
- Lin-curve 3
Lin-curves 1 … 3 can be edited by the
user (see appropriate chapter).
Param.
TAG-
No. 1
Adjust-
ment
Signal
condit-
ioning
TAG -
No. 1
%
xx,x
Scaling
Lin.
curve
linear
0%
corres-
ponds
0
100%
corres-
ponds
1000
Integr
ation
time s
0
Density
in
Kg/dm
3
1,000
Meas.
value
limita-
tion
Deci-
mal
point
888,8
prop.
to
unde-
fined
Unit
– –
nega-
tive
values
yes
Failure
mode
Stan
dard
DK
value
(Er)
81,00
spherical tank…
>110%
After scaling or linearisation, the required
output must be assigned to the scaled or
linearised value (menu item "prop. to..." and
"Unit...") in the menu range "Parameter adjust-
ment of outputs".
Under
Meas. value limitation,
you can ex-
clude negative values.
Failure mode Standard
means that at a sensor current of 3.6 mA or
21 mA, the fail safe relay responds.
Failure mode >110%
generates a fault signal if a meas. value of
more than 110 % or less than -10 % is
reached.