VEGAMET 614
13
Adjustment
4 Adjustment
4.1 Indicating and adjustment
elements
A rotary switch is located on the upper side
of the housing. It is used to set the instrument
address on DISBUS. This setting is neces-
sary if several VEGAMET signal conditioning
instruments are linked via the DISBUS or if
you control a VEGADIS 174 indicating instru-
ment via the DISBUS.
The adjustment range 1 … F corresponds to
the DISBUS addresses 1 … 15.
Factory setting: 1
Note:
If address 0 is set, the VEGAMET does not
participate in the DISBUS communication.
Rotary switch
The set instrument address on the DISBUS
can be indicated via the LC display.
Note
If several VEGAMET are linked via the
DISBUS, each address must be assigned
only once!
Rotary switch
Front plate
1 LCD (4 lines with 6 figures each, illuminated) for clear text
indication
2 LED chain (yellow) for quasianalogue indication of the
measured value
3 Keys for menu adjustment
4 Connection socket for VEGACONNECT
5 LED (yellow) lights if the relay is energised (standard
setting)
6 LED (red), lights if fail safe relay is deenergised
7 LED (green), lights if operating voltage is on
Ser. No.
12345678
CONNECT
%
100
+
-
OK
ESC
on
1
2
614
1
2
3
4
5
6
7
8
7
6
5
4
0
F
E
D
C
B
A
9
3 3
2
1
10
11
12
13
14
15
Position of the rotary switch