VEGAMET 614

21

Settings in the "Reduced menu“

Adjustment example

You know the data of the sensor, i.e. you
know that at 0 % filling, the sensor delivers a
current of 4.2 mA and at 100 % filling a cur-
rent of 15.5 mA. Enter these values in the
menu items.

6.3 Adjustment without medium

For this adjustment procedure, you have to
enter two sensor current values (4 … 20 mA)
corresponding to the levels 0 % and 100 %.

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

with
medium

w.o
medium

0%
at

mA

4,000

100%
at
mA

20,000

Meas.
value
indication

Enter in these two menu items the values of
the senor. Use the [+] and [–] keys to set the
values and [OK] to save the values.

0%
at
mA

4,200

100%
at
mA

15,500

4.2 mA at 0 %

15.5 mA at 100 %