VEGAMET 514V
MET indication/PC/PLC outputs/DIS outputs
Settings in the "extended menu“
MET indication/Unit:
In the menu item "prop. to“ you choose the
parameter to which the VEGAMET display
reacts (if you have carried out a scaling un-
der the menu item "Signal conditioning“,
"prop. to scaled“ will have been automatically
adjusted, i.e. the display will indicate the
scaled value). "Prop. to volume“ is then useful
if you have selected, for example, a spherical
tank or a user-programmable lin. curve under
"Signal conditioning - Linearisation curves“.
The indicated values of the VEGAMET
display then react proportionally to the
volume of the tank contents.
PC/PLC outputs and DIS outputs:
Are adjusted according to the same scheme
as the MET indication.