Met indication/pc/plc outputs/dis outputs – VEGA VEGAMET 514V User Manual

Page 40

background image

40

VEGAMET 514V

MET indication/PC/PLC outputs/DIS outputs

Settings in the "extended menu“

MET indication/Unit:

In the menu item "prop. to“ you choose the
parameter to which the VEGAMET display
reacts (if you have carried out a scaling un-
der the menu item "Signal conditioning“,
"prop. to scaled“ will have been automatically
adjusted, i.e. the display will indicate the
scaled value). "Prop. to volume“ is then useful
if you have selected, for example, a spherical
tank or a user-programmable lin. curve under
"Signal conditioning - Linearisation curves“.
The indicated values of the VEGAMET
display then react proportionally to the
volume of the tank contents.

PC/PLC outputs and DIS outputs:

Are adjusted according to the same scheme
as the MET indication.

Param.
TAG-
No. 2

like TAG-No. 1

Param.
TAG-
No. 1

Adjust-
ment

Signal
condi-
tioning

Out-
puts

Cur-
rent
out-
puts

Volt
out-
puts

MET
display

PC/PLC
outputs

DIS
outputs

DIS
output
1

PC/PLC
output 1

Unit

0,0%

DIS
output
7

PC/PLC
output 7

prop.
to

Per-
cent

Unit

0,0%

prop.
to

Per-
cent

Unit

0,0%

like DIS output 1

like PC/PLC output 1

TAG -
No. 1
%
xx,x

prop.
to

Per-
cent

Relay
out-
puts

scaled
Height

scaled
Height

scaled
Height