4 adjustment without medium – VEGA VEGAMET 514V User Manual
Page 19

VEGAMET 514V
19
Settings in the "reduced menu“
6.4 Adjustment without medium
For this adjustment procedure, you have to
enter two values (pressure or distance) cor-
responding to the levels 0 % and 100 %.
Adjustment example
You know that your vessel is actually
filled up to 80%. Move to the menu
item "Max. adjust at % 100.0“. Push
the [–] key briefly, so that the figure
100.0 flashes (editing mode).
Continue pushing [–] until the figure
80.0 appears on the display. Now
push [OK] to save the adjustment.
Later, when your filling is, for exam-
ple, 10 %, you move to the menu item
"Min. adjust at % 0.0“. Briefly push
[+], until the figure 0.0 flashes
(editing mode).
Continue pushing [+] until "10“ ap-
pears on the display. Now push [OK]
to save the adjustment.
You can of course carry out the adjustment
with medium at 0 % and 100 % filling. Note:
The figures 0 % and 100 % must flash (edit-
ing mode), before they can be saved with the
[OK] key.
Max-
adjust
at %
100,0
Max-
adjust
at %
80,0
Min-
adjust
at %
0,0
Min-
adjust
at %
10,0
TAG-
No. 1
%
xx,x
Param.
TAG-
No. 1
Ad-
just-
ment
with
medium
without
medium
0%
at
bar
0,000
100%
at
bar
1,000
Meas.
value
indication
Adjust-
ment
bar
m