6 integration time, Settings in the "reduced menu – VEGA VEGAMET 514V User Manual
Page 21
VEGAMET 514V
21
Settings in the "reduced menu“
6.6 Integration time
Percent
Pressure
Mass
prop.
to
Height
Unit
m
dm
cm
….
TAG -
No. 1
m
2,341
TAG-
No. 1
%
xx,x
Param.
TAG-
No. 1
Ad-
just-
ment
Signal
condi-
tioning
Scal-
ing
Integr
ation
time s
0
Meas.
value
indication
If the integration time is set to 0 s (factory
setting), each quick change of the product
surface (e.g. waves) will be immediately
detected and interpreted as level change. All
output values of VEGAMET will follow the
wave movements. To avoid this, the integra-
tion time can be increased (max. 600 s are
possible with VEGAMET). The higher the time
setting, the slower the measured value
display reacts.
100 %
0 %
h=1.5 m
h=4.5 m
Scaling example
You have a raised tank and you want the
level to be indicated in meters with three
places after the decimal point.
Adjust the figure 1500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 0 % (if
you want to have a lower resolution of
the meas. value indication, you can also ad-
just 150 or 15).
Adjust the figure 4500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 100 %.
Adjust the decimal point as shown
(with keys [+], [–] and [OK]).
Choose the term "Height“ in this
menu item (with keys [+], [–] and
[OK]).
If you have chosen "Height“ in the
previous menu item, you get a choice
of several units (mm, dm, cm, m,
yard…). Choose m (with the keys
[+], [–] and [OK]).
In the meas. value indication, the
scaled value is shown.
0%
corres-
ponds
1500
100%
corres-
ponds
4500
Deci-
mal
point
8,888
2.341 m