7 adjustment – VEGA VEGAMET 514V User Manual
Page 34
34
VEGAMET 514V
Settings in the "extended menu“
7.7 Adjustment
The
adjustment with medium
corresponds
to the procedure in the reduced menu (see
appropriate chapter).
- if the medium is changed later on (medium
with another density value) and no new
adjustment can be made
or
- if the MET indication and the DIS outputs
relate to height in meters
note the following:
In applications with hydrostatic pressure
transmitters, the adjusted density value must
correspond to the value of the medium.
For the
adjustment with medium,
two an-
ticipated values for level, pressure etc. cor-
responding to 0 % and 100 % must be
entered.
The menu item "Offset correction“ is activated
when hydrostatic pressure transmitters are
connected. The offset correction should be
carried out after installation of the sensor, as
the sensor values can differ slightly due to
different installation positions or strong tight-
ening during mounting.
With the offset correction, the meas. data of
the unpressurised sensor (vessel empty) are
detected as correction values and taken into
account in all subsequent measurements.
Param.
TAG-
No. 1
Adjust-
ment
with
medium
without
medium
Min-
adjust
at %
0,0
Max-
adjust
at %
100,0
Adjust-
ment
bar
Offset
correc-
tion
0%
at
bar
0,000
100%
at
bar
5,000
Sensor
unpres-
sur’d?
OK ?
Offset
corr.
Now!
OK ?
TAG -
No. 1
%
xx,x
Param.
TAG-
No. 2
like TAG-No. 1
Signal
condi-
tioning
Scaling
Lin.
curve
linear
Integr
ation
time s
0
Density
in
Kg/dm
3
1,000