9 parameter adjustment of outputs, Current outputs/volt outputs, Settings in the "extended menu – VEGA VEGAMET 514V User Manual
Page 36
36
VEGAMET 514V
Settings in the "extended menu“
7.9 Parameter adjustment of outputs
Current outputs/Volt outputs
In the menu item "
prop. to
“ you can choose
between percent and volume. "Prop. to vol-
ume“ is then useful when under "Signal condi-
tioning - Linearisation curves“, for example, a
spherical tank or an individually defined
linearisation curve is selected. The output
current or the output voltage is then propor-
tional to the volume of the tank contents.
Unit:
Selection list dependent on the choice in the
previous menu item "prop. to“ (see chapter "8
Measuring results and units“).
Volt output/Current output:
If "free“ is chosen, the following (light grey)
menu items appear:
- Volt at 0 %/100 %:
Individual voltage values between 0 V and
+10 V can be adjusted.
- Current at 0 %/100 %:
Individual current values between 0 mA
and +20 mA can be adjusted.
Failure mode:
The height of the output current/output volt-
age in case of failure is determined. If "--“ is
chosen, the actual value is maintained.
Volt limitation/Current limitation on:
Voltage/current remain within the values
which are given in the menu item voltage
output/current output.
Volt
output
2
like Volt output 1
Current
output
2
like
current output 1
Param.
TAG-
No. 2
like TAG-No. 1
Param.
TAG-
No. 1
Adjust-
ment
Signal
condi-
tioning
Out-
puts
Cur-
rent
out-
puts
Volt
out-
puts
Cur-
rent
output
1
Volt
output
1
prop.
to
Per-
cent
Unit
0,0%
prop.
to
Per-
cent
Unit
0,0%
TAG -
No. 1
%
xx,x
Volume
TARE%
Volume
TARE%
Volt
output
0/10V
Failure
mode
0V
Volt
limita-
tion
on
Volt
at
0%
0,000
Volt
at
100%
10,000
10/2V
10/0V
2/10V
free
0,0
..10,0
0,0
..10,0
11V
- -
0%
100%
off
Current
output
4/20mA
Failure
mode
0mA
Current
limita-
tion
on
Cur-
rent at
0%
4,000
Current
at
100%
20,000
0/20mA
20/4mA
20/0mA
free
0,0
..20,0
0,0
..20,0
22mA
- -
0%
100%
off