beautypg.com

VEGA VEGASON 54V…56V User Manual

Page 87

background image

VEGASON 54V … 56V

87

Setup - Adjustment with the PC on VEGALOG

• Confirm your adjustments with

"OK“ and

you are again in the menu window "

Adjust-

ment“.

• Click in the menu window "

Adjustment“ to

"

Quit“.

You are again in the menu window "

Instru-

ment data parameter adjustment“.

Now the sensor electronics has two charac-
teristics points, one for min. and one for max.,
out of which a linear correlation between
product distance and the percentage filling of
a vessel is generated. Naturally the charac-
teristics point must not be at 0 % and 100 %,
however the distance should be as big as
possible (e.g. at 20 % and at 80 %). The
difference between the characteristics points
for the min./max. adjustment should be at
least 50 mm product distance.

This is a theoretical value, because if the
characteristics points are too close together,
the possible measuring error increases. Ideal
would be, to carry out the adjustment as
shown in the example, at 0 % and at 100 %.In
the menu "

Instrument data/Parameter adjust-

ment/Conditioning/Linearisation“ you can
enter later, if necessary, a correlation be-
tween product distance and percent value of
volume other than linear (see later subitem
linearisation).

Conditioning

• Click in the menu window "

Instrument data

parameter adjustment“ to "

Conditioning“.

The menu window "

Conditioning“ opens.

• Click to "

Scaling“.

In the menu "

Scaling“ you enter the actual

0 % and 100 % values of the parameter and
their unit. You thereby inform the sensor, e.g.
that at 0 % filling there are still 45 liters and at
100 % filling 1200 liters in the vessel. The
sensor display then shows with empty vessel
(0 %) 45 liters and with full vessel (100 %)
1200 liters.