Operating range, Meas. conditions, Adjustment – VEGA VEGASON 54V…56V User Manual
Page 69
VEGASON 54V … 56V
69
The distance indication flashes
and you can choose "feet“ and
"m“.
Confirm the adjustment with
"
OK“.
Adjustment without medium
(adjustment independent of the actual level)
Key adjustment
Display indication
Adjust-
ment
Para-
meter
Sensor
m(d)
4.700
w.o
medium
Adjust-
ment
in
m(d)
(min. adjustment)
OK
OK
+
OK
OK
OK
Adjust-
ment
in
m(d)
0.0%
at
m (d)
XX.XXX
OK
+
–
or
With"
+“ and "–“ you adjust the
percentage value for the min.
value or the lower level (exam-
ple 0.0 %).
The adjusted percentage
value is written in the sensor
and the distance corres-
ponding to the percentage
value flashes.
With the "
+“ or "–“ key you can
assign a level distance (ex-
ample 5.85 m) to the previ-
ously adjusted percentage
value. If you do not know the
distance, you have to do a
sounding.
Max.
Min.
100 % (1.270 m) correspond
to 1200 liters
Span (4.58 m)
0 % (5.850 m) corresponds
to 45 liters
4. Operating range
Without special adjustment, the operating
range corresponds to the measuring range.
The measuring range has already been ad-
justed with the min./max. adjustment. Gener-
ally it is useful to choose a slightly bigger
(approx. 5 %) operating range than the
measuring range.
Example:
Min./max. adjustment: 0.500 … 3.500 m;
adjust operating range to approx.
0.400 … 3.600 m.
5. Meas. conditions
(see menu schematic page 78)
2. Adjustment
Under the menu item "
Adjustment“ you inform
the sensor with which measuring range it
should operate.
You can carry out the adjustment without and
with medium. Generally you will carry out the
adjustment without medium, as you can then
adjust without a filling cycle.
Setup - Adjustment with VEGAMET or MINICOM
+
–
or