beautypg.com

Vessel installations, Struts – VEGA VEGASON 54V…56V User Manual

Page 35

background image

VEGASON 54V … 56V

35

Buildup

If the sensor is mounted too close to the
vessel wall, buildup and adhesions of the
measured product to the vessel wall can
cause false echoes. Position the sensor at a
sufficient distance from the vessel wall.
Please also note chapter "4.2 General instal-
lation instructions“.

Inflowing material

Do not mount the instrument in or above the
filling stream. Ensure that you detect the
product surface and not the inflowing mate-
rial.

Mounting and installation

Vessel installations

Vessel installations such as, for example, a
ladder, often cause false echoes. Make sure
when planning your measurement loop that
the ultrasonic signals have free access to the
measured product.

Vessel installations

Correct

Wrong

Ladder

Ladder

Struts

Struts, like other vessel installations, can
cause strong false echoes that are superim-
posed over the useful echo signals. Small
shields effectively hinder a direct false echo
reflection. These false echoes are scattered
and diffused in the area and are then filtered
out as "echo noise“ by the measuring elec-
tronics.

Struts

Correct

Wrong

Shields

Inflowing material

Correct

Wrong

Correct

Wrong