VEGA VEGASON 54V…56V User Manual
Page 56
56
VEGASON 54V … 56V
Setup - Adjustment with the PC on VEGAMET
False echo storage
With the menu item "
False echo storage“ in
the menu "
Sensor optimisation“ you can au-
thorise the sensor to save false echoes. The
sensor electronics then saves the false ech-
oes in an internal database and assigns them
a lower level of importance than the useful
echo. The false echo storage should be car-
ried out with empty vessel.
• Click in the menu window to "
Sensor optimi-
sation“ to the menu item
"False echo stor-
age. A small window opens.
• Now click in the opening menu window
"
False echo storage“ to
"Learn false ech-
oes.
• Enter here the verified product distance
and click to
"Create new.
You hereby authorise the sensor to mark all
echoes before the product echo as false
echoes. This prevents the sensor from erro-
neously detecting a false echo as level echo.
• Click to
"Show echo curve.
The curve and the false echo marking are
shown.
• Quit the menu with
"Quit.
You are again in the menu window "
Sensor
optimisation“. With the menu item "Reset“ you
reset all options out of the menu "
Sensor
optimisation“ to default.
• Quit the menu window "
Sensor optimisa-
tion“ with
"Quit and the menu window
"
Sensor optimisation sensor selection“ also
with "
Quit“.
You are then in the initial menu window "
In-
strument data parameter adjustment“.
• Click to the menu item
Meas. loop data.