VEGAPULS 51 V … 54 V
Set-up
-
Adjustment with the PC on VEGALOG
Parameter adjustment
In the menu "
Instrument data/Parameter
adjustment" you carry out all important
sensor adjustments.
Adjustment
• Choose the menu
"
Instrument data/Parameter adjustment
Instrument data/Parameter adjustment
Instrument data/Parameter adjustment
Instrument data/Parameter adjustment
Instrument data/Parameter adjustment",
and then the sensor for which you want to
carry out the parameter adjustment.
In the heading of the opening menu window
you now see the previously adjusted
measurement loop name and the
measurement loop description.
When you have only configured one sensor
on the signal conditioning instrument,
naturally only one sensor is available.
• First choose "
Adjustment
Adjustment
Adjustment
Adjustment
Adjustment"
• Then click in the menu window "Adjustment"
to "
Min / Max - adjustment
Min / Max - adjustment
Min / Max - adjustment
Min / Max - adjustment
Min / Max - adjustment"
You can carry out the Min./Max.-adjustment
"with medium" (adjustment by means of the
real level) or
"without medium" (without
considering the real level, i.e. also with empty
vessel).
Generally you will carry out the adjustment
without medium, so you are completely inde-
pendent of the actual vessel filling.
When you want to carry out the adjustment
with medium, you have to carry out the min.
adjustment with emptied (also partly
emptied) vessel and the max. adjustment
with filled (also partly filled) vessel.
It is hence comfortable and quick to carry out
the adjustment without medium like in the
example.
• Choose "
no (adjustment without medium)
no (adjustment without medium)
no (adjustment without medium)
no (adjustment without medium)
no (adjustment without medium)"
• Choose in the following window if you want
to carry out the adjustment in metres (m) or
in
Feet (ft).
• Enter a distance
distance
distance
distance
distance for the upper and lower
level and the appropriate filling degree
filling degree
filling degree
filling degree
filling degree in
%.
In the example the 0 % filling is at a level
distance of 3,400 m and the 100 % filling at a
level distance of 0,500 m.