3 technical data, 1 data – VEGA VEGAPULS 51V…54V User Manual
Page 18
18
VEGAPULS 51 V … 54 V
Power supply
Supply voltage
from signal conditioning instrument VEGAMET or
processing system VEGALOG 571
(max. 36 V DC)
fuse 0,5 A
(slow-blow)
Current consumption
max 22,5 mA
Power consumption
max. 80 mW
0,45 VA
Meas. range
1)
Standard
0 … 20 m
Measurement in standpipe
- VEGAPULS 54 on DN 50
0 … 16 m
- VEGAPULS 54 on DN 100
0 … 19 m
Output signal (see "Outputs and processings")
Digital meas. signal (VBUS)
Adjustment
- PC with adjustment software VEGA Visual Operating
- adjustment module MINICOM
Accuracy (typical values under reference conditions)
2)
Linearity error
< 0,1 % (relating to max. meas. range)
Average temperature error
0,03 %/10 K
Accuracy of the 4 … 20 mA
0,25 %
output signal
Resolution
1 mm
Characateristics
Meas. frequency
5,8 GHz (USA 6,3 GHz)
Meas. intervals
1 s
Min. span between
full and empty adjustment
> 10 mm (recommended >50 mm)
Beam angle (at –3 dB)
- VEGAPULS 51 … 53
< 24°
- VEGAPULS 54 with DN 80
38°
- VEGAPULS 54 with DN 100
30°
- VEGAPULS 54 with DN 150
20°
Technical data
2)
Reference conditions acc. to IEC 770:
e.g. temperature 18 … 30°C
1)
Min. distance of the antenna to the medium 5 cm
3 Technical data
3.1 Data