• First click to "

Meas. environment

Meas. environment

Meas. environment

Meas. environment

Meas. environment".

The window "

Meas. environment" opens

With the menu point "

Measuring range" you

can define the measuring range of the sensor
deviating from the "

Min/Max-Adjustment".

As a standard feature the measuring range
normally corresponds to the min./max.
adjustment.

Generally it will be suitable to choose the
measuring range approx. 5 % larger than the
range determined by the min./max.
adjustment.
In the example: Min. adjustment to 0,500 m,

max. adjustment to 3,400 m.

• Save the adjustments with "

OK

OK

OK

OK

OK"

• Click in the menu window "

Meas.

environment" to "Measuring condition

Measuring condition

Measuring condition

Measuring condition

Measuring condition".

• In the menu window "

Measuring conditions"

you click to the options corresponding to
your application.

• Confirm with "

OK".

After some seconds of saving during which
the adjustments are saved in the sensor, you
are again in the window "

Meas. environment".

• Click in the menu window "

Meas.

environment" to "Quit

Quit

Quit

Quit

Quit".

You are again in the menu window "

Sensor

optimisation".

Echo curve

With the menu point "

Echo curve" you can

look at the course and the strength of the
detected radar echo.

If due to vessel installations, strong false
echoes have to be expected, a correction of
the installation position (if possible) can help
to localize and reduce the size of the false
echo by monitoring the echo curve.

Set-up

-

Adjustment with the PC on VEGAMET