VEGAPULS 51 V … 54 V

Adjustment with medium

Fill the vessel e.g. to 10 % and enter in the
menu "

Min. set" with the "+" and "–" keys

10 %. Then fill the vessel e.g. to 80 % or
100 % and enter in the menu "

Max. set" with

the "

+" and "–" keys 80 % or 100 %.

If you do not know the distance, you have to
sound.

The indication stops flashing
and the adjustment will be
saved.

Hence you have adjusted the min. value.

Set-up

-

Adjustment with MINICOM or VEGAMET

(max. adjustment)

The max. adjustment is made like the min.
adjustment with "

+", "–" or "OK" (example:

1,270 m).

Note:

Note:

Note:

Note:

Note:
The sensor can only detect levels within the
defined operating range. For level detection
outside the operating range, the operating
range must be corrected appropriately in the
menu "Sensor optimisation/meas.
environment" (under figure 2.).

with
Medium

Min-
Adjust-
ment at
%

XXX.X

Max-
Adjust-
ment at
%

XXX.X

Now you can enter with the "

+" and "–" key

the distance, which your sensor has to the
product at 0 % filling (example: 5,850 m)

OK

100.0%

at

m (d)

XX.XXX

5.) Conditioning / Scaling

Under the menu point "

Conditioning/Scaling"

you enter the figure which corresponds to a
0 % and 100 % filling and choose beside the
position of the decimal point a physical unit,
e.g. distance.

Enter in the menu window "

0 % corresponds"

to the value of the 0 %-filling (in the example
of the adjustment with PC this was 45 for 45
litres).
Confirm with "

OK".

With the

key you change to the 100 %

menu. Enter the value of your parameter
corresponding to a 100 %-filling. In the
examble this had been 1200 for 1200 litres.
Confirm with "

OK".

If necessary choose a decimal point.
However note that only max. 4 digits can be
displayed.
In the menu "

prop. to" you choose the

parameter (mass, volume, distance…) and in
the menu "

Unit" the physical unit (kg, l, ft

3

, gal,

m

3

…).

Signal
conditi-
oning

Scaling

0 %
corres-
ponds

XXXX

100 %
corres-
ponds

XXXX

Deci-
mal-
point

888.8

prop.
to

undef-

ined

Unit

Kg