Analog_input objects (cont.) – Veris Industries E51H5 Install User Manual
Page 28

ZL0109-0C
Page 28 of 32
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E51H2, E51H5
TM
#
Object
Name
Description
R/W
NV
Units
Range
Additional Information
AI65
PF_B
Power Factor Phase B
R
-1.00 - 1.00
AI66
PF_C
Power Factor Phase C
R
-1.00 - 1.00
AI67
Volts_AB
Voltage Phase A-B
R
Volts
AI68
Volts_BC
Voltage Phase B-C
R
Volts
AI69
Volts_AC
Voltage Phase A-C
R
Volts
AI70
Volts_AN
Voltage Phase A-N
R
Volts
AI71
Volts_BN
Voltage Phase B-N
R
Volts
AI72
Volts_CN
Voltage Phase C-N
R
Volts
AI73
Current_A
Current Phase A
R
Amps
AI74
Current_B
Current Phase B
R
Amps
AI75
Current_C
Current Phase C
R
Amps
AI76
Max_Power
Max Power
R
NV
kW
AI77
Reserved_
AI77
(Reserved AI77)
R
Returns QNAN or any value
AI78
Energy_Resets Count of Energy_
Resets
R
NV
AI79
Reserved_
AI79
(Reserved AI79)
R
Returns QNAN or any value
AI80
Reserved_
AI80
(Reserved AI80)
R
Returns QNAN or any value
AI81
Power_Up_
Count
Count of Power Up
Cycles
R
NV
AI82
Output_
Config
Output Configuration
R
NV
0-15
E51H2 returns “11”
E51H5 returns “10”
AI83
Alarm_Bitmap Alarm Bitmap (all of
BI1-BI15)
R
NV
Analog_Input Objects (cont.)