Installation Guide

Power Monitoring

E51H2, E51H5

TM

Property

R/W

NV

Value Returned

Additional information

Object_List

R

NV

DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI1

0,AI11,AI12,AI13,AI14,AI15,AI16,AI17,AI1

8,AI19,AI20,AI21,AI22,AI23,AI24,AI25,AI2

6,AI27,AI28,AI29,AI30,AI31,AI32,AI33,AI3

4,AI35,AI36,AI37,AI38,AI39,AI40,AI41,AI4

2,AI43,AI44,AI45,AI46,AI47,AI48,AI49,AI5

0,AI51,AI52, AI53, AI54, AI55, AI56, AI57,

AI58, AI59, AI60, AI61, AI62, AI63, AI64,

AI65, AI66, AI67, AI68, AI69, AI70, AI71,

AI72, AI73, AI74, AI75, AI76, AI77, AI78,

AI79, AI80, AI81, AI82, AI83, AV1,AV2,AV3,

AV4,AV5,AV6,AV7,AV8,AV9,AV10,AV11,BI1

,BI2,BI3,BI4,BI5,BI6,BI7,BI8,BI9,BI10,BI11,

BI12,BI13,BI14,BI15,TL1,TL2,TL3

BI15, TL1, TL2, and TL3 are present on the E51H5 only.

Device_Address_Binding

R

NV

{}

Database_Revsion

R

NV

0

Analog_Value
Objects

Use the Present_Value property of the Analog_Value object for all writable variables in the meter other than those used
specifically for BACnet configuration, Time Synchronization (in the Device Object), or Data Logging (in the Trend_Log objects).

Values are checked when written, and errors are returned for invalid entries. This table describes how the meter uses those
variables, what values are valid, and what their defaults are. When writing values to the Present_Value properties of Analog_
Value BACnet objects, there is a delay of up to about two seconds to validate and store the new value. An immediate read of the
same property before that delay has elapsed can return the prior value (even if the new value was accepted). To read a value
immediately after writing it, check the Reliability property first. When it reports a No_Fault_Detected status, the Present_Value
of the object is current.

These objects support the Description and Reliability object properties and all required Analog_Value object properties, but
Present_Value is the only writable property.

#

Name

Description R/W

NV

Units

Range

Factory

Default

Value

Additional information

AV1

Config

Configuration R/W

n/a

n/a

Always

returns

”0” when

read

Command Register:
- Write 30078 (0x757E) to clear all energy accumulators to 0 (All).
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle and log

another data value on Trend_Log objects TL1-TL3 (when the meter is in Manual “Sync-

to Comms” mode). This takes effect at the end of the next 1 second calculation cycle.

Write no more frequently than every 10 seconds. Trend_Log values are only present on

the E51H5 model.

- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes

effect at the end of the next 1 second calculation cycle. Write no more frequently than

every 10 seconds.

- Write 16498 (0x4072) to clear pulse counters to 0.

AV2

System_Type System Type

R/W

NV

n/a

40, 31, 12,

11, 10

40

System_Type:
- Write 10 for Single-Phase: A + N
- Write 11 for Single-Phase: A + B
- Write 12 for Split-Phase: A + B + N
- Write 31 for 3-Phase Δ: A + B + C, no N
- Write 40 for 3-Phase Y: A + B + C + N

AV3

CT_Ratio_

Primary

CT Ratio -

Primary

R/W

NV

Amps

5-32000

100

Current Transducer Size - Primary Current Range (Default is set for 100 A CTs)

AV4

CT_Ratio_

Secondary

CT Ratio -

Secondary

R/W

NV

1/Volts

1,3

1

Current Transducer Type – Secondary Interface
- Enter 1 for CTs with 1V outputs (Default)
- Enter 3 for CTs with 1/3V outputs

Device Object (cont.)